The configuration and regulatory compliance of Plant Central Controllers (CCI) represent critical steps in the commissioning process of renewable energy plants. The requirements of the CEI 0-16 standard and the integration of communication logic towards DSOs (Distribution System Operators) demand the accurate parameterization of numerous factors: from managing Modbus communication channels with field devices to configuring the data required by Annex 11.
To reduce operational variability in the field and standardize setup procedures, Higeco More has integrated the new CCI Configuration Wizard on board its devices. The interface transforms the configuration into a guided, linear, and verifiable workflow at every single stage.
Software architecture and integration logic
The Configuration Wizard is designed to guide the technician step by step through the CCI configuration, providing a structured, fast, and error-free path.
From both an architectural and functional standpoint, the Wizard is designed to ensure stability, lightweight performance, and operational efficiency:
The operational structure of the Configuration Wizard
The interface divides the configuration into two main sections, broken down into guided sub-steps.
1. General data
The first main section manages system settings and device connectivity through 4 steps:
- General data: setting of device identification parameters, including name, date, time, and GPS coordinates.
- Network configuration: setup of the local network and network interfaces.
- Server: definition of addressing and communication parameters towards the reference servers.
- Plant data: entry of the general plant specifications, POD code, nominal grid voltage, and information required by Annex 11.
2. Peripheral configuration
The second main section covers the mapping and parameterization of communication channels and field devices via Modbus, broken down into 8 steps:
- PdC Meter: automatic generation of the Point of Delivery meter.
- Additional meters: configuration of any auxiliary plant meters.
- Protection relays: configuration of the grid interface protection.
- Gateways & smart loggers: association of data concentrators and third-party monitoring devices.
- Generators: mapping of inverters and photovoltaic generation units.
- Loads: entry and categorization of plant power consumption (available from December).
- Sensors: integration of environmental sensors (irradiance, temperature, and wind).
- Applying the configuration: writing parameters to memory, automatic configuration of control plugins (PID and Governor), and execution of the real-time communication test with field peripherals.
Operational planning: when to use the Configuration Wizard
The Configuration Wizard was designed to natively and intuitively manage the complete setup of standard photovoltaic plants, automatically generating and parameterizing the PID (P and Q) and Governor plugins.
For plants with more complex architectures or special logic—such as EMS profiles, feed-in limitations, or hybrid multi-technology systems—the Wizard provides an ideal foundation: it enables operators to quickly model the plant structure and field devices, leaving only the parameterization of specific controls to the system’s advanced screens.
Higeco More Academy: become a Certified Integrator
In addition to providing advanced software tools like the Wizard, Higeco More supports industry professionals through its Certified Integrators Program. This training program is designed to deliver advanced expertise and ensure high operational standards across all types of plants.
1. ONLINE CCI COURSE
2. LIVE CCI COURSE
3. ON-SITE TRAINING
To consolidate these hands-on skills in the field, Higeco More Academy’s live courses enable professionals to master the practical use of the new Configuration Wizard, delve into CEI 0-16 testing procedures, and streamline on-site commissioning times.
This way, earning certification means not only mastering Higeco More’s operational tools, but also gaining access to priority technical support channels and acquiring the skills needed to confidently manage the most complex projects.
Want to master CCI configuration with the new Wizard and become a Higeco More Certified Integrator? 👉 Discover the program and register for the upcoming Live sessions!